CALCULATING THE ERROR FOR A FLOWMETER INSTALLED IN THE WRONG SIZE PIPE

An insertion flowmeter is specified for a 14-inch pipe. What will be the approximate flow measurement error if the flowmeter is installed in an 18-inch pipe?
  • a. Increase flow by 40 percent
  • b. Increase flow by 20 percent
  • c. No effect
  • d. Decrease flow by 20 percent
  • e. Decrease flow by 40 percent

Source: www.flowcontrolnetwork.com - Author: David W. Spitzer